Sign In | Join Free | My tjskl.org.cn |
|
Brand Name : NBSe/OEM
Model Number : DZ30LE-32
Certification : CE
Place of Origin : CHINA
Pole number : 2P , 1P+N
Rated Voltage : 230V
Rated Current : 6,10,16,20,25,32A
Protection : MCB+RCCB
Residual current : 30mA
Function : Leakage protection
Mounting : Din-rail type
Type : mini
Standard : IEC/EN61009
Product name : RCBO,Electrical RCCB/RCD/ELCB
Application : household,Terminal distribution,Electrical Power,widely,Electricity Distribution Room
Material : Fire proof PA66
DZ30LE-32 63a RCBO DPNL 230V 1P+N Residual current Leakage RCBO
General description
RCBO used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V, used as electron shock protection. It can protect circuit form overload and short circuit. This product has advantages of small volume, high breaking capacity, live and zero wire are cut off at the same time, also protecting person from electric shock when the live wire connected opposite. It conforms with the standards of IEC61009.
EARTH FAULT PROTECTION
AC 50Hz/60Hz
rated voltage 230V
used as electron shock protection
It can protect circuit form overload and short circuit
DZ30LE-32 63a RCBO DPNL 230V 1P+N Residual current Leakage RCBO
Main Technical Parameter
1)Provides protection against earth fault/leakage current, short-circuit,overload,and function of isolation. | |||||||||||
2)Contact position indication. | |||||||||||
3)Provides protection against indirect contact by human body. | |||||||||||
4)Provides complementary protection against direct contact by human body. | |||||||||||
5)Effectively protects electric equipment against insulating failure. | |||||||||||
6)Equipped with switched neutral and phase pole . | |||||||||||
7)Provides protection against over-voltage. | |||||||||||
8)Provides comprehensive protection to household and commercial distribution systems. | |||||||||||
Technical Data | |||||||||||
9)Type: Electronic type | |||||||||||
10)Residual current characteristics: AC | |||||||||||
11)Pole No.: 1P+N | |||||||||||
12)Tripping curve: B,C,D | |||||||||||
13)Rated short-circuit capacity: 4.5KA | |||||||||||
14)Rated Current(A): ,10,16,20,25,32,40,63 | |||||||||||
15)Rated Voltage:230V AC | |||||||||||
16)Rated Frequency:50/60Hz | |||||||||||
17)Rated residual operating current(mA): 0.03,0.1,0.3 | |||||||||||
18)Tripping duration:instantaneous under or equal 0.1s | |||||||||||
19)Electro-mechanical: pillar terminal with clamp. | |||||||||||
20)Terminal Connection Height: H1=16mm ,H2=21mm | |||||||||||
21)Over-votage tripping: 280V±5% | |||||||||||
22)Connection capacity: Flexible conductor 10mm2 , Rigid conductor 16mm2 . | |||||||||||
23)Installation: On symmetrical DIN rail 35mm, Panel mounting | |||||||||||
Accessories | |||||||||||
24) S2 Shunt Tripper | |||||||||||
25) U2+O2 Over-voltage and under-votage tripp |
The over-current protection property
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | Note |
Cold position | 1.13In | t ge 1h | Non-release | - | |
30plusmn2oC | Carried out immediately after previous test | 1.45In | t<1h | Release | - |
Cold position | 2.55In | 1s < t < 60s | Release | Current smoothly rises to specified value within 5s | |
-5~+40oC | Cold position | 5In | t ge 0.1s | Non-release | Type C |
Cold position | 10In | t < 0.1s | Release | Type C |
DZ30LE-32 63a RCBO DPNL 230V 1P+N Residual current Leakage RCBO
ABOUT US
Founded in 1993, Wenzhou New Blue Sky Electrical Co., Ltd(Former Yueqing Blue Sky Electrical Co., Ltd)is situated in beautiful Wuniu Industrial Park, Wenzhou City at the bank of Oujiang River; it is a high and new-tech enterprise professionally researching, developing, and manufacturing miniature circuit breakers and residual current circuit breakers. The company has been awarded honors such as “AAA-grade Export Credit Enterprise”, “Advanced Enterprise”, “Star Enterprise”, and “Patent Model Enterprise” in successive years.
![]() |
Electrical Terminal Distribution DPNL 2 Pole 32A RCBO Breaker Images |